30 Connections
panel.
Power input wiring does not require shielding (screening) if the power is fed to the enclosure via metal
conduit. If metal conduit is not used in the system, shielded cable is required on the power input wires
along with proper bonding techniques.
Filtering
CE Filtering
Apply proper bonding and grounding techniques, described earlier in this section, when incorporating
EMC noise filtering components to meet this standard.
Noise currents often occur in two ways. The first is conducted emissions passed through ground loops.
The quality of the system-grounding scheme inversely determines the noise amplitudes in the lines.
These conducted emissions are of a common-mode nature from line-to-neutral (ground). The second is
radiated high-frequency emissions that usually are capacitively coupled from line-to-line and are
differential in nature.
When mounting the filters, make sure the enclosure has an unpainted metallic surface. This allows more
surface area to be in contact with the filter housing and provides a lower impedance path between the
housing and the back plane. The back panel should have a high frequency ground strap connection to the
enclosure frame and earth ground.